Below 8°, 16.5 mm corrugate is out. This comparison is the next CoP rows. Full family notes: NZ longrun profiles. Product page for Hi Five: Hi Five on a low-pitch job. Calculator: trapezoidal.

Profile Min cladding pitch Cover (library) Check run Notes
Dimond Six Rib 760 mm (820 mm overall) 20 m ~20 mm rib. Usual step down from corrugate.
Dimond Hi Five 765 mm (some sheets 755 mm; 810 mm overall) 40 m ~27 mm five-rib. South Island supply listed.
Metalcraft T-Rib 760 mm 40 m Same CoP row as Hi Five; different roll. Do not mix.
Tray / secret-fix typically 3° override (library 300 mm) product sheet Clips, pans, seams — not a rib count.

Minima are cladding pitch after deflection. A 3° drawing with wide purlins can still pond. Do not “sealant” a profile under its table.

Count and run

Cover, not overall: 9.2 m ÷ 0.765 m = 12.03 → 13 Hi Five sheets. Using 810 mm gives 12 and a shortage.

Long + flat is a drainage problem. Record run separately from width. Hi Five’s 40 m check is longer than Six Rib’s 20 m; a 22 m Six Rib at 4° should not get a silent pass. Tray run and clip spacing are on that pan’s sheet.

Flashings at low pitch and Extra High need Category B covers (flashing checklist). Waste still follows hips and valleys.

Pick by the limiting condition

Open the takeoff, set the named profile and the actual pitch, and read the min-pitch and run warnings before coil is cut. NZMRM CoP and the manufacturer sheet remain the authority.